    2074

    Valve for INERT GAS fixed extinguisher

    Valve for fixed fire suppression systems using inert gases, according with Directive 2014/68/EU, for use with 80L to 140L cylinders at 200 and 300 bar. Valve designed in compliance to the guidelines of EN 12094-4 Suitable for a… See more...
    Standard Specifications
    Inlet: 1"-11.5 NPT
    Outlet: G 3/4"
    Fracture disc: 400/650 bar
    Dip tube connection: G 1/2"
    Actuator connection: M30x1.5
    Pressure gauge connection: M10x1
    Options
    Models:
    • 200 bar (Safety disc calibration: 270 +/- 10bar)
      300bar (Safety disc calibration: 430 +/- 15bar)